ASTM E-1623, I-Cal

Western Fire Center Laboratories

1/2" cellulose ceiling tiles
Test Report #WFC98054

FM 4975 (Hydrocarbon)

Factory Mutual Approvals Lab

1/2" cellulose ceiling tiles

ASTM E 84, Steiner Tunnel Test

Omega Laboratories (Intertek Testing Labs)

1/2" Cement board
Test Report # OMEGA 15810-110128

AS 1530.4 Australia Standard 60/60/60 Rating Ceiling System

Straw fiber cement panels
Proprietary 3rd party fire test, Australian National University

AS 1530.4 Australia Standard 60/60/60 Rating

8mm Cement fiberboard panels
Proprietary 3rd party fire test

ASTM E 119, 2 Hr Ceiling System

Western Fire Center Laboratories

2 3/4" Concrete slab-floors
Test Report # WFC 01011

ASTM E 84, Steiner Tunnel Test

Southwest Research Institute

1 1/2" Fiberglass/Foam PVC acoustic panels
Test Report # SWRI 01-6739-144a

BSS-7239-88, Boeing Toxicity Test

Omega Laboratories (Intertek Fire Testing Labs)

1/4" Fiberglass
Test Report # OMEGA 15810-103929

ASTM E 1354-94, Cone Calorimeter

Omega Laboratories (Intertek Fire Testing Labs)

1/4" fiberglass panels
Test Report # OMEGA 15810-102686

AS 1530.4 Australia Standard

DEPARTMENT OF DEFENCE, SCIENCE AND TECHNOLOGY

Polyester GRP composites

ASTM E 662-97, Smoke Density Test

SGS U.S. Testing Company

1/8" fiberglass transit panels
Test Report # SGS 164641-2, BART

ASTM E 162-98, Radiant Heat Energy Source

SGS U.S. Testing Company

1/8" fiberglass transit panels
Test Report # SGS 164641-1, BART

FAR 25.853-1 Flammability Fire Test

Fiberglass seat back Boeing 747, B/E Aerospace/Seating Products Group
Written Report # SPG-CL-1259A, Proprietary fire test by FAA

Other

Proprietary Tests

1/4" fiberglass sculpture, 3rd party proprietary fire test @ Intertek Laboratories
Mandalay Bay Las Vegas
Fiberglass/carbon fiber
Bombardier business Learjet, 3rd party proprietary fire test by FAA
6 mm Fiber cardboard sculpture, 2000 microns tested to 15 min Room Fire Test
Proprietary fire test, Sydney Harbor Restaurant

UBC 26-3, Room Corner Test

Radco Laboratories

6" semi-rigid, low density polyurethane foam
Test Report # RAD-3321

ASTM E-84, Steiner Tunnel Test

South West Research Institute Laboratories

1 1/2" fiberglass/foam PVC acoustic panels
Test Report # SWRI 01-6739-144a

ASTM E-84, Steiner Tunnel Test

Omega Laboratories (Intertek Testing Laboratories)

2" rigid foam Co-Polymer
Test Report # OMEGA 16941-118444
1.5" polyurethane modified polyisocyanurate foam
Test Report # Dow 15824-124680

UBC 26-2, Thermal Barrier Test

Western Fire Center, Inc Laboratories

24 gauge steel exterior skin polyurethane foam interior.
Test Report # WFC 99063
1/4" Gypsum board skin, polyurethane foam 1/16" fiberglass skin.
Test Report # WFC 01084.T3
7/16" Oriented Strand Board (OSB) exterior skin, polystyrene foam interior.
Test Report # WFC 99070

ASTM E 662-97, Smoke Density Test

Omega Point Laboratories (Intertek Testing Labs)

ITW 3/4" Polyurethane foam filters
Test Report # OMEGA 16288-108753

ASTM E-3675-98, Radiant Panel Test

Omega Laboratories (Intertek Testing Laboratories)

ITW 3/4" Polyurethane foam filters
Test Report # OMEGA 16288-108756

ASTM E-1623, I-Cal Tests

Western Fire Center Laboratories

2" Polyurethane foam with steel plate
Test Report #WFC 98054

ASTM E 119, Polyimide Foam

Omega Laboratories (Intertek Testing Laboratories)

Wall panel test on SOLIMIDE HT-340 foam

UBC 26-3 Room Corner Test

Western Fire Center Laboratory

1/2" Type-X Gypsum and 1/2" AC Plywood
Test Report # WFC 04008

FM 4975 Ceiling Test

Factory Mutual Approvals Lab

1/2" Gypsum board
Test Report # FM4975

ASTM E-119, 1 Hr Wall System

Western Fire Center Laboratory

1/2" sheetrock 2x4 wood studs @ 16" o.c.
Test Report # WFC 00089 T1&T2
5/8" sheetrock 2x4 wood studs @ 16"o.c. (Gypsum lawsuit).
Test Report # WFC 99064 T1.
5/8" gypsum board, 20, 40, 60 mils
Test Report # WFC 99055 T1.T2.T3

AS 1530.4 Australia Standard 60/60/60 Rating

CSIRO Testing Laboratory

13mm non rated plasterboard
Test Report # FSV 0653, Assessment Number FCO 1698

ASTM E-119, 2 Hr Wall System

Western Fire Center Laboratory

1 layer 5/8" sheetrock non-load bearing on 2x4 wood studs @16"o.c.
Fire Engineering Assessment Letter

ASTM E-119, 2 Hr Wall System

Forest Laboratory, University of California

2 layers 5/8" sheetrock, loaded stud wall with 9 built in defects.
Test Report # SIP No. 35.04.439

ASTM E-119, 1 Hr Ceiling System

Western Fire Center Laboratory

5/8" type-X sheetrock, single layer on 2x10 joists @ 16"o.c. w/ defective nailing, with 5/8" T &G Plywood sub-floor.
Test Report # WFC99053 3.T1
Single layer 5/8" type-X sheetrock on 2x10 joists @ 24"o.c. with defective nailing with 5/8" T &G Plywood sub-floor.
Test Report # WFC99053 2.T3
Single layer 5/8" type-X sheetrock over RC channel @ 24"o.c. with 2x8 joists @ 16"oc. with 3/4" T&G Plywood sub-floor.
Test Report # WFC99067 T1.T2.T3.T4
Single layer 5/8" type-X sheetrock with BCI 450 I Joists, wood studs @ 16"o.c. with OSB
Test Report # WFC No. 00019 T1T2T3

ASTM E-119, 1 Hr Ceiling System

Intertek / Warnock Hersey Testing Laboratories

Single layer 5/8" type-X sheetrock over RC channel @ 24"o.c. with 9 1/2"-250 series TJI @ 19.2"oc.
Test Report # WHI-495-PSH-0245

ASTM E-119, 2 Hr Ceiling System

Western Fire Center, Inc Laboratories

Defective U.L assembly BXUV-G524 where 1/2" type-C was required & 1/2" non-rated was installed.
Fire Engineering Assessment Letter, Sagamore Towers
Single layer 5/8" type-X sheetrock with nominal 2x10 joists @ 16"o.c. with 3/4" plywood sub-floor & 3/4" gypcrete.
Fire Engineering Assessment Letter, Residence Inn

ASTM E-1623, I-Cal

Western Fire Center, Inc Laboratories

5/8" sheetrock
Test Report # WFC 98054

BSS-7239-88, Boeing Toxicity Test

Anderson Laboratories Report

1/2' sheetrock

ASTM E 119, 1 Hr Wall System

Western Fire Center, Inc Laboratories

1" thick plaster attached to metal wall studs @ 16"o.c.
Fire Engineering Assessment Letter, 666 Folsom Street
1/2" wood lath & plaster, 2x4 wood studs @ 16"o.c.
Test Report # WFC 01084 (ran to failure; 93 minutes)

ASTM E 119, 1 Hr Ceiling System

Western Fire Center, Inc Laboratories

7/8" plaster over metal lath fastened to trusses @ 24"o.c. with R-30 insulation.
Fire Engineering Assessment Letter, Woodland Church project.

ASTM E 119, 2 Hr Wall System

Western Fire Center Laboratories

10 gage galvanized sheet metal plate
Test Report # WFC 99053

ASTM E 119, 1 Hr Ceiling System

Western Fire Center Laboratories

Embossed tin attached to 1"x2" wood w/ 4x10 joists 12"o.c. and 1 1/2" wood flooring.
Test Report # WFC 00050 T1

AS 1530.4 Australia Standard 60/60/60 Rating

CSIRO Testing Laboratory

Pressed metal ceiling
Assessment Number FCO 2278

ASTM E 119, 2 Hr Ceiling System

Western Fire Center Laboratories

Embossed Tin over 3/8"" rock board attached to nominal 3x10 joists @ 16"o.c. with 1/4" wood sub-floor with suspended T-Bar ceiling.
Fire Engineering Assessment Letter & Structural Calculations, Westwood Church

15-Mt Thermal Barrier (UBC 26-2/IBC 26-2)

Western Fire Center, Inc Laboratories

7/16" Oriented Stand Board (OSB) exterior skin, polystyrene foam interior.
Test Report # WFC 99070
1/2" AC Plywood
Test Report # WFC 04008

15-Mt Room Corner Test, FM 4880 (UBC 26-3/IBC 26-3)

Factory Mutual Laboratories

5/8" CDX plywood
Test Report # Factory Mutual 3020954

15-Mt Hydrocarbon Ceiling Test, FM 4975

Factory Mutual Laboratories

1x4 Douglas Fir T&G
Test Report # Factory Mutual 3019443

Room Corner Test (UBC 8-2), sand burner 50kw/m2 5 min, 160kw/m2 10 min

University of California / Forest Products Laboratories at Berkeley

5/8" Douglas fir; test resulted in no flame spread, smoke or room flashover
1/2" Masonite board siding
Cedar shingles
1/4" Mahogany paneling
7/16" Oriented Strand Board siding
7/16" Lap Siding


Fire Doors Tests



ASTM E-119 – 45 minutes, negative pressure

Warnock Hersey Test Laboratories

1 3/8" non-rated solid core door, ASTM E-119, 45 minutes at negative pressure.
Test Report # WHI-495-1569

ASTM E-119 – 30 minutes, positive pressure

Singapore Institute of Standards and Industrial Research (SISIR)

5/16" mahogany plywood panel (5) in solid wood (1 3/4") rails, 30 minutes at
Test Report # SISIR 96003

ASTM E-84, Steiner Tunnel Test

Omega Point Laboratories

1x4" Douglas Fir T&G
Test Report # 15810-111045

ASTM E-84, Steiner Tunnel Test

Underwriter Laboratories

7/16" Oriented Strand Board.
Test Report # R14654

ASTM E-84-08 (30 minutes)

Intertek Testing Laboratories

1/2" Plywood panels
Report Number Intertek 3167621SAT-002

British Standard 476 Part 6 & 7

BRE Global Laboratories

12mm Timber Boards
Test Report #s BRE 262682 and BRE 259490

AS 1530.3 Australia Standard Flame/Smoke Rating

CSIRO Testing Laboratory

11mm Plywood, Test Report # FNE 7715
(0-20) Ignitability - 1
(0-20) Spread of Flame - 0
(0-10) Heat evolved - 0
(0-10) Smoked Developed - 4

Flammability Standards (FAR Part 25) Section 25.853

Australian Wool Testing Authority Ltd

Timber pallets
Test Report # 7-513964-CN

ASTM E 119, 1 Hr Wall System

Western Fire Center, Inc Laboratories

7/16" timberline hardboard siding on stud wall.
Test Report # WFC 01003
5/8" fire treated plywood each side of 6" metal studs.
Fire Engineering Assessment Letter
3/4" T & G wood veneer over 5/8 gypsum, over wall studs.
Fire Engineering Assessment Letter
1/2" plywood shear wall over 2x6 studs @ 16" o.c.
Fire Engineering Assessment Letter
1/2" Oriented Stand Board (OSB) over 3x6 wood studs @ 16"o.c.
Fire Engineering Assessment Letter

AS 1530.4 Australia Standard 30/30/30 Rating

CSIRO Testing Laboratory

20mm pine weatherboard at both sides of 90mm x 45mm, 2"x4" studs
Test Report # FSV 0989

AS 1530.4 Australia Standard 60/60/60 Rating

CSIRO Testing Laboratory

Timber horizontal test
Assessment Number FC0 2638

AS 1530.4 Australia Standard 120/120/120 Rating

CSIRO Testing Laboratory

Masonry walls
Test Report # FSV 0653, Assessment Number FC0 2638

ASTM E 119, 1 Hr Ceiling System

Western Fire Center Laboratory

Exposed 2x6 T &G Pine with 3" Polyisocyanurate foam, 2x4 sleepers & 1/2" CDX Plywood sheathing.
Test Report # WFC99079 T2.
Exposed full dimensional 2x10 joists @ 16"o.c. with 1 3/4" wood sub-floor with 3 1/2" fiberglass insulation @ joists
Fire Engineering Assessment Letter, Mercy Gardens
Exposed full dimensional 2x10 joists @ 16"o.c. with exposed 13/4" wood sub-floor
Fire Engineering Assessment Letter & Structural calculations, Women’s Facility
2x14 joists @ 16"o.c. with 2 layers. 3/4" Plywood sub-floor with 3 1/2" mineral wood insulation between joists with suspended sheetrock ceiling.
Fire Engineering Assessment Letter, 37 & 39 South 1st St
2x4 web trusses @ 24" o.c. with 3/4" plywood roof sheathing with 3 1/2" polyisocyanurate foam and roof membrane.
Fire Engineering Assessment Letter, Ruby’s Dinner
Assorted glue lam beams; 2 1/4" mini-lams; 2x10 joists and 5/8" OSB floor sheathing.
Structural calculations, Avignon Apartments
Roof system, glue lams.
Structural calculations, Abundant Life Church

ASTM E 119, 2 Hr Ceiling System

Western Fire Center Laboratory

Exposed 3x10 joists @ 16"o.c. with 4 3/4" wood layered sub-floor.
Test Report # WFC 00124 T1

ASTM E-1623, I-Cal

Western Fire Center Laboratory

Medium cedar shakes. WFC 98054
5/8" T-111 Douglas fir siding
5/8" AC plywood
1/2" OSB
1/4" mahogany paneling